Condition h3>
For example, AUPD 2 boosta 50-1501 KCR , where
">">>
- AUPD -Automated setting to increase pressure
- 2 -the total number of electric pumps;
- Boosta 50-1501 -type of main pump unit;
- KCR -CCR-cascade-frequency regulation, CR-frequency regulation
For example, aupd 2 boosta 50-1501 p boosta 25-205 , where:
">">>
- AUPD -Automated pressure installation;
- 2 -the total number of electric pumps;
- Boosta 50-1501 -type of main pump unit;
- P - Type of regulation: P- for fire extinguishing systems;
- Boosta 25-205 -type of pumping pump (for the sprinkler system)
Appointment h3>
Automated pressure installation provides the following functions:
">">>
-
-
-
-
-
Design
Pressure increases are pumping stations, which include 2 to 4 multi-stage vertical pumps Boosta.
Boosta pumps are installed on a common frame and are interconnected by suction and pressure pipelines. The connection of the pumps to the collectors is performed using locking reinforcement and check valves.
The control cabinet is fixed on the rack installed on the frame.
Colgroup>
Brands
Feed (range), m³/h
Pressure (range), m
Number of pumps, pcs.
TR>
AUPD ... Boosta 40-10 ... KCR DIV>
5 ... 56
1.5 ... 145
2 ... 4
TR>
AUPD ... Boosta 40-10 ... CR DIV>
5 ... 56
1.5 ... 145
2 ... 4
TR>
AUPD ... Boosta 50-15 ... KCR DIV>
8 ... 96
2 ... 138
2 ... 4
TR>
AUPD ... Boosta 50-15 ... CR DIV>
8 ... 96
2 ... 138
2 ... 4
TR>
AUPD ... Boosta 50-22 ... KCR DIV>
11 ... 116
1.5 ... 148
2 ... 4
TR>
AUPD ... Boosta 50-22 ... CR DIV>
11 ... 116
1.5 ... 148
2 ... 4
TR>
AUPD ... Boosta 65-33 ... KCR DIV>
15 ... 160
2.5 ... 149
2 ... 4
TR>
AUPD ... Boosta 65-33 ... CR DIV>
15 ... 160
2.5 ... 149
2 ... 4
TR>
AUPD ... Boosta 80-46 ... KCR DIV>
22 ... 240
2 ... 149
2 ... 4
TR>
AUPD ... Boosta 80-46 ... CR DIV>
22 ... 240
2 ... 149
2 ... 4
TR>
AUPD ... Boosta 100-66 ... KCR DIV>
30 ... 340
3 ... 140
2 ... 4
TR>
AUPD ... Boosta 100-66 ... CR DIV>
30 ... 340
3 ... 140
2 ... 4
TR>
AUPD ... Boosta 100-92 ... KCR DIV>
45 ... 480
3 ... 133
2 ... 4
TR>
AUPD ... Boosta 100-92 ... CR DIV>
45 ... 480
3 ... 133
2 ... 4
TR>
AUPD ... Boosta 125-125 ... KCR DIV>
45 ... 640
2.5 ... 110
2 ... 4
TR>
AUPD ... Boosta 125-125 ... CR DIV>
45 ... 640
2.5 ... 110
2 ... 4
TR>
AUPD ... Boosta 40-10 ... n
5 ... 56
4 ... 145
2 ... 4
TR>
AUPD ... Boosta 50-15 ... n
8 ... 96
5 ... 138
2 ... 4
TR>
AUPD ... Boosta 50-22 ... n
11 ... 116
3 ... 148
2 ... 4
TR>
AUPD ... Boosta 65-33 ... n
15 ... 160
6.5 ... 149
2 ... 4
TR>
AUPD ... Boosta 80-46 ... n
22 ... 240
4.5 ... 149
2 ... 4
TR>
AUPD ... Boosta 100-66 ... n
30 ... 340
8 ... 140
2 ... 4
TR>
AUPD ... Boosta 100-92 ... n
45 ... 480
7.5 ... 133
2 ... 4
TR>
AUPD ... Boosta 125-125 ... n
45 ... 640
6 ... 110
2 ... 4
TR>
AUPD ... Boosta 40-10 ... n boosta 25-2 ...
5 ... 56
4 ... 145
2 ... 4
TR>
AUPD ... Boosta 50-15 ... n boosta 25-2 ...
8 ... 96
5 ... 138
2 ... 4
TR>
AUPD ... Boosta 50-22 ... n boosta 25-2 ...
11 ... 116
3 ... 148
2 ... 4
TR>
AUPD ... Boosta 65-33 ... n boosta 25-2 ... DIV>
15 ... 160
6.5 ... 149
2 ... 4
TR>
AUPD ... Boosta 80-46 ... n boosta 25-2 ... DIV>
22 ... 240
4.5 ... 149
2 ... 4
TR>
AUPD ... Boosta 100-66 ... n boosta 25-2 ... DIV>
30 ... 340
8 ... 140
2 ... 4
TR>
AUPD ... Boosta 100-92 ... n boosta 25-2 ... DIV>
45 ... 480
7.5 ... 133
2 ... 4
TR>
AUPD ... Boosta 125-125 ... n boosta 25-2 ...
45 ... 640
6 ... 110
2 ... 4
TR>
For example, AUPD 2 boosta 50-1501 KCR , where
- ">">>
- AUPD -Automated setting to increase pressure
- 2 -the total number of electric pumps;
- Boosta 50-1501 -type of main pump unit;
- KCR -CCR-cascade-frequency regulation, CR-frequency regulation
For example, aupd 2 boosta 50-1501 p boosta 25-205 , where:
- ">">>
- AUPD -Automated pressure installation;
- 2 -the total number of electric pumps;
- Boosta 50-1501 -type of main pump unit;
- P - Type of regulation: P- for fire extinguishing systems;
- Boosta 25-205 -type of pumping pump (for the sprinkler system)
Appointment h3>
Automated pressure installation provides the following functions:
">">>
-
-
-
-
-
Design
Pressure increases are pumping stations, which include 2 to 4 multi-stage vertical pumps Boosta.
Boosta pumps are installed on a common frame and are interconnected by suction and pressure pipelines. The connection of the pumps to the collectors is performed using locking reinforcement and check valves.
The control cabinet is fixed on the rack installed on the frame.
Colgroup>
Brands
Feed (range), m³/h
Pressure (range), m
Number of pumps, pcs.
TR>
AUPD ... Boosta 40-10 ... KCR DIV>
5 ... 56
1.5 ... 145
2 ... 4
TR>
AUPD ... Boosta 40-10 ... CR DIV>
5 ... 56
1.5 ... 145
2 ... 4
TR>
AUPD ... Boosta 50-15 ... KCR DIV>
8 ... 96
2 ... 138
2 ... 4
TR>
AUPD ... Boosta 50-15 ... CR DIV>
8 ... 96
2 ... 138
2 ... 4
TR>
AUPD ... Boosta 50-22 ... KCR DIV>
11 ... 116
1.5 ... 148
2 ... 4
TR>
AUPD ... Boosta 50-22 ... CR DIV>
11 ... 116
1.5 ... 148
2 ... 4
TR>
AUPD ... Boosta 65-33 ... KCR DIV>
15 ... 160
2.5 ... 149
2 ... 4
TR>
AUPD ... Boosta 65-33 ... CR DIV>
15 ... 160
2.5 ... 149
2 ... 4
TR>
AUPD ... Boosta 80-46 ... KCR DIV>
22 ... 240
2 ... 149
2 ... 4
TR>
AUPD ... Boosta 80-46 ... CR DIV>
22 ... 240
2 ... 149
2 ... 4
TR>
AUPD ... Boosta 100-66 ... KCR DIV>
30 ... 340
3 ... 140
2 ... 4
TR>
AUPD ... Boosta 100-66 ... CR DIV>
30 ... 340
3 ... 140
2 ... 4
TR>
AUPD ... Boosta 100-92 ... KCR DIV>
45 ... 480
3 ... 133
2 ... 4
TR>
AUPD ... Boosta 100-92 ... CR DIV>
45 ... 480
3 ... 133
2 ... 4
TR>
AUPD ... Boosta 125-125 ... KCR DIV>
45 ... 640
2.5 ... 110
2 ... 4
TR>
AUPD ... Boosta 125-125 ... CR DIV>
45 ... 640
2.5 ... 110
2 ... 4
TR>
AUPD ... Boosta 40-10 ... n
5 ... 56
4 ... 145
2 ... 4
TR>
AUPD ... Boosta 50-15 ... n
8 ... 96
5 ... 138
2 ... 4
TR>
AUPD ... Boosta 50-22 ... n
11 ... 116
3 ... 148
2 ... 4
TR>
AUPD ... Boosta 65-33 ... n
15 ... 160
6.5 ... 149
2 ... 4
TR>
AUPD ... Boosta 80-46 ... n
22 ... 240
4.5 ... 149
2 ... 4
TR>
AUPD ... Boosta 100-66 ... n
30 ... 340
8 ... 140
2 ... 4
TR>
AUPD ... Boosta 100-92 ... n
45 ... 480
7.5 ... 133
2 ... 4
TR>
AUPD ... Boosta 125-125 ... n
45 ... 640
6 ... 110
2 ... 4
TR>
AUPD ... Boosta 40-10 ... n boosta 25-2 ...
5 ... 56
4 ... 145
2 ... 4
TR>
AUPD ... Boosta 50-15 ... n boosta 25-2 ...
8 ... 96
5 ... 138
2 ... 4
TR>
AUPD ... Boosta 50-22 ... n boosta 25-2 ...
11 ... 116
3 ... 148
2 ... 4
TR>
AUPD ... Boosta 65-33 ... n boosta 25-2 ... DIV>
15 ... 160
6.5 ... 149
2 ... 4
TR>
AUPD ... Boosta 80-46 ... n boosta 25-2 ... DIV>
22 ... 240
4.5 ... 149
2 ... 4
TR>
AUPD ... Boosta 100-66 ... n boosta 25-2 ... DIV>
30 ... 340
8 ... 140
2 ... 4
TR>
AUPD ... Boosta 100-92 ... n boosta 25-2 ... DIV>
45 ... 480
7.5 ... 133
2 ... 4
TR>
AUPD ... Boosta 125-125 ... n boosta 25-2 ...
45 ... 640
6 ... 110
2 ... 4
TR>
Automated pressure installation provides the following functions:
- ">">>
- Design
Pressure increases are pumping stations, which include 2 to 4 multi-stage vertical pumps Boosta.
Boosta pumps are installed on a common frame and are interconnected by suction and pressure pipelines. The connection of the pumps to the collectors is performed using locking reinforcement and check valves.
The control cabinet is fixed on the rack installed on the frame.
Brands | Feed (range), m³/h | Pressure (range), m | Number of pumps, pcs. | TR>
AUPD ... Boosta 40-10 ... KCR DIV>
|
5 ... 56 | 1.5 ... 145 | 2 ... 4 | TR>
AUPD ... Boosta 40-10 ... CR DIV>
|
5 ... 56 | 1.5 ... 145 | 2 ... 4 | TR>
AUPD ... Boosta 50-15 ... KCR DIV>
|
8 ... 96 | 2 ... 138 | 2 ... 4 | TR>
AUPD ... Boosta 50-15 ... CR DIV>
|
8 ... 96 | 2 ... 138 | 2 ... 4 | TR>
AUPD ... Boosta 50-22 ... KCR DIV>
|
11 ... 116 | 1.5 ... 148 | 2 ... 4 | TR>
AUPD ... Boosta 50-22 ... CR DIV>
|
11 ... 116 | 1.5 ... 148 | 2 ... 4 | TR>
AUPD ... Boosta 65-33 ... KCR DIV>
|
15 ... 160 | 2.5 ... 149 | 2 ... 4 | TR>
AUPD ... Boosta 65-33 ... CR DIV>
|
15 ... 160 | 2.5 ... 149 | 2 ... 4 | TR>
AUPD ... Boosta 80-46 ... KCR DIV>
|
22 ... 240 | 2 ... 149 | 2 ... 4 | TR>
AUPD ... Boosta 80-46 ... CR DIV>
|
22 ... 240 | 2 ... 149 | 2 ... 4 | TR>
AUPD ... Boosta 100-66 ... KCR DIV>
|
30 ... 340 | 3 ... 140 | 2 ... 4 | TR>
AUPD ... Boosta 100-66 ... CR DIV>
|
30 ... 340 | 3 ... 140 | 2 ... 4 | TR>
AUPD ... Boosta 100-92 ... KCR DIV>
|
45 ... 480 | 3 ... 133 | 2 ... 4 | TR>
AUPD ... Boosta 100-92 ... CR DIV>
|
45 ... 480 | 3 ... 133 | 2 ... 4 | TR>
AUPD ... Boosta 125-125 ... KCR DIV>
|
45 ... 640 | 2.5 ... 110 | 2 ... 4 | TR>
AUPD ... Boosta 125-125 ... CR DIV>
|
45 ... 640 | 2.5 ... 110 | 2 ... 4 | TR>
AUPD ... Boosta 40-10 ... n
|
5 ... 56 | 4 ... 145 | 2 ... 4 | TR>
AUPD ... Boosta 50-15 ... n
|
8 ... 96 | 5 ... 138 | 2 ... 4 | TR>
AUPD ... Boosta 50-22 ... n
|
11 ... 116 | 3 ... 148 | 2 ... 4 | TR>
AUPD ... Boosta 65-33 ... n
|
15 ... 160 | 6.5 ... 149 | 2 ... 4 | TR>
AUPD ... Boosta 80-46 ... n
|
22 ... 240 | 4.5 ... 149 | 2 ... 4 | TR>
AUPD ... Boosta 100-66 ... n
|
30 ... 340 | 8 ... 140 | 2 ... 4 | TR>
AUPD ... Boosta 100-92 ... n
|
45 ... 480 | 7.5 ... 133 | 2 ... 4 | TR>
AUPD ... Boosta 125-125 ... n
|
45 ... 640 | 6 ... 110 | 2 ... 4 | TR>
AUPD ... Boosta 40-10 ... n boosta 25-2 ...
|
5 ... 56 | 4 ... 145 | 2 ... 4 | TR>
AUPD ... Boosta 50-15 ... n boosta 25-2 ...
|
8 ... 96 | 5 ... 138 | 2 ... 4 | TR>
AUPD ... Boosta 50-22 ... n boosta 25-2 ...
|
11 ... 116 | 3 ... 148 | 2 ... 4 | TR>
AUPD ... Boosta 65-33 ... n boosta 25-2 ... DIV>
|
15 ... 160 | 6.5 ... 149 | 2 ... 4 | TR>
AUPD ... Boosta 80-46 ... n boosta 25-2 ... DIV>
|
22 ... 240 | 4.5 ... 149 | 2 ... 4 | TR>
AUPD ... Boosta 100-66 ... n boosta 25-2 ... DIV>
|
30 ... 340 | 8 ... 140 | 2 ... 4 | TR>
AUPD ... Boosta 100-92 ... n boosta 25-2 ... DIV>
|
45 ... 480 | 7.5 ... 133 | 2 ... 4 | TR>
AUPD ... Boosta 125-125 ... n boosta 25-2 ...
|
45 ... 640 | 6 ... 110 | 2 ... 4 | TR>