Centrifting hermetic hermetic screen transformer electriciner TE is designed to ensure the circulation of transformer oil in cooling systems of power transformers of stationary installations.
Electrolysis is designed for long-term operation from the temperature of the transformer oil up to 80 ° C and a short-term (2 hours) up to 95 ° C.
Electroxy is released in climatic design U1 GOST 15150-69.
Electric pump installation-external, on open air in conditions of moderate or cold climate at temperatures from minus 45 ° C to plus 40 ° C.
Electric pump is allowed up to 3000 m.
Electric pump function is allowed not exceeding 9 points (short -term work for no more than 20 seconds in vibrational loads with a frequency of 0.5 to 120 Hz with an acceleration of 3G). ); Font-Family: Verdana, Arial, Helvetica, Sans-Serif; Font-Size: 13px; Text-align: Justify; Background-Color: RGB (75, 134, 199); " />
The operating mode of the electric pump-Long-term S1 According to GOST 183-74. The electric pump can be installed horizontally or vertically (absorbing pipe up).
The pump design is constantly modernized and improved .
in the conditional designation, as an example Electric pump TE 100/15 U1, numbers and letters indicate:
Nominal feed | 100 m³/h | TR>
Naporte at nominal feed | 15m | TR>
Rotation frequency | 3000 rpm | TR>
Permissible cavitation supply | 5 | TR>
Efficiency | 40% | TR>
Voltage | 220/380 TD> TR> |
Phase connection | Triangle/Star TD> TR> |
Current at nominal feed | 220V-22.6A/380V-13.8a | TR>
Nominal engine power | 11 kW | TR>
Heating resistance class | F | TR>
The multiplicity of the starting current | 7.3 | TR>
R isol. stator relative to the case (cold/slave) | 3.2/1.0 mom | TR>
The mass is no more, kg | 130 | TR>