Centrifting hermetic transformer electric pump brand MT 100/15 U1 is designed to ensure the circulation of transformer oil in cooling systems of power transformers of stationary installations.
Electrolysis is designed for long-term operation from the temperature of the transformer oil up to 80 ° C and a short-term (2 hours) up to 95 ° C.
Electroxy is released in climatic design U1 GOST 15150-69.
Electric pump installation-external, on open air in conditions of moderate or cold climate at temperatures from minus 45 ° C to plus 40 ° C.
Electric pump is allowed up to 3000 m. The functioning of an electric pump is allowed in conditions of seismicity not exceeding 9 points.
The operating mode of the electric pump-Long-term S1 According to GOST 183-74. The electric pump can be installed horizontally or vertically (absorbing pipe up).
El. energy supplied to the electric pump according to GOST 13109-97.
The pump design is constantly modernized. < /span>
In the conditional designation of the MT 100 electric pump /15 U1 numbers and letters indicate:
Nominal feed | 100 m³/h | TR>
Naporte at nominal feed | 15m | TR>
Rotation frequency | 3000 rpm | TR>
Permissible cavitation supply | 5 | TR>
Efficiency | 56% | TR>
Voltage | 220/380 TD> TR> |
Phase connection | Triangle/Star TD> TR> |
Current at nominal feed | 220V - 22.6A / 380V - 13.8A TD> TR> |
Nominal engine power | 5.5 kW | TR>
Heating resistance class | In | TR>
The multiplicity of the starting current | 7.3 | TR>
R isol. stator relative to the case (cold/slave) | 3.2/1.0 mom | TR>
The mass is no more, kg | 150 | TR>